Product Highlights
The EOI output is a separate dry Form A contact that signals the end of a metering interval, with a customer-selectable fixed duration of 100, 300, 500, or 1000 milliseconds, or a “long” mode that follows the actual EOI signal duration. A dedicated yellow LED in the customer compartment displays EOI status independently of the energy pulse LEDs, giving technicians clear visual confirmation of all three outputs simultaneously.
All three outputs use solid-state switching devices rated at 800V and 750mA, and built-in transient suppression eliminates the need for external suppressors. Coordinated double “K” lead fusing across both compartments protects against overcurrent and wiring faults, and input/output isolation is rated at 2500Vrms.
Features
- Three isolated outputs — one field-selectable Form A or Form C customer output, one fixed utility Form C output, and one Form A EOI contact.
- End-of-Interval (EOI) output — dedicated dry Form A contact with selectable fixed duration (100, 300, 500, or 1000mS) or actual EOI signal duration.
- Dual-compartment NEMA 4X enclosure — locked utility compartment and separate customer compartment in a single weatherproof ready-to-use package.
- Two customer-accessible switches — independently select output mode (2-wire or 3-wire) and EOI timing duration without utility access.
- Coordinated dual-compartment fusing — double "K" lead fusing across utility and customer compartments for fast fault isolation.
- 800V/750mA solid-state switching — provides maximum protection from lightning and transient voltage damage across all outputs.
- Three-LED status display — red, green, and yellow LEDs in the customer compartment independently indicate energy pulse and EOI output status.


Dual KYZ plus EOI interface
Can't Find What You're Looking For?