RD-31 Dytronic Three-Phase Reference Standard

Features

Measurement

The RD-31 registers both forward and reverse energy flow and provides voltage, current, power and energy (Active, Reactive, Apparent) information.

Meter and Standard Testing

The RD-31 can be used with a controlled current source to test revenue meters and reference standards. In field applications the RD-31 can perform a true three phase meter accuracy test using existing service load.

Analog Sense

The RD-31’s Optional analog sense feature enables testing transducers and energy meters that provide an analog output from zero to 2 mA.

 

Overview

PRODUCT HIGHLIGHTS

The Radian RD-31 Three-phase Electricity Reference Standard achieves a level of accuracy and performance never before available in a portable standard.                  

The RD-31 utilizes Radian’s new Dytronic measurement technology consisting of a Radian designed Integrating Analog to Digital Signal Converter. Unlike off-the-shelf A/D Converters used in other instruments, Radian’s A/D Converter is specifically designed and optimized for power and energy measurement. This unique design makes the RD-31 absolutely unsurpassed in its ability to accurately measure “real world” waveforms. The RD-31’s A/D Converter is combined with Radian’s renowned electronically compensated voltage and current input transformers and a hermetically sealed reference set to provide the highest degree of accuracy, stability and versatility offered in a portable three-phase standard.

MEASUREMENTS

The RD-31 is a four quadrant three-phase measuring instrument that registers both forward and reverse energy flow and provides per phase voltage, current, power and energy (Active, Reactive, Apparent) information.

ANALOG SENSE

The optional analog sense feature enables testing of transducers and electronic energy meters that provide an analog current output from zero to 2 mA.

METER  AND  STANDARD  TESTING

The RD-31 can be used with a controlled current source to test revenue meters and reference standards. In field applications the RD-31 can perform a true three phase meter accuracy test using existing service load. Pickups to sense meter disk rotation or calibration pulses of infrared, visible light or KYZ variety plug directly into the unit. The RD-31 is ideal for testing high end energy meters found in power plants, substations, inter-tie points and at large utility customer accounts. The RD-31 is also the perfect complement to relay test sets where it can serve as an active reference standard when testing meters or can be used to periodically certify the accuracy of the test set itself.

Technical Data

Package Contents

  • RD-31 Standard
  • RD-2x and RD-3x Manual CD
  • RD-2x and RD-3x Getting Started Guide
  • Cables

RD-3X Specifications

Unless stated specifications apply to the Radian Model RD-30, RD-31 and RD33.  All accuracy specifications are guaranteed and include traceable accuracy to calibration standards used, 95% confidence level. Specifications are for 365 day calibration interval.

General

Operating Range:

 

Current

0.02 to 120 Amp, (200 Amp optional)

Voltage

30 to 630 Vac (60Hz), 30 to 525 Vac (50Hz)

Aux Power

60 to 630 V (autoranging)

Frequency

45 Hz to 65 Hz

PF Accuracy

Power Factor

RD-30

RD-31

RD-33

> 0.5

0.04 %

0.02 %

0.01 %

 0.5

0.04 %/2PF

0.02 %/2PF

0.01 %/2PF

Harmonic Analysis

< 64th (bandwidth 10000 Hz)

Dimensions:

5"(127 mm), 17.5" (444.5 mm), 6.25" (158.7 mm)

Weight:

16 lbs (7.2 kg), Shipping weight 28 lbs (12.6 kg)

Environment:

 

Operating & Storage Temp.

-20°C to +70°C

Humidity

0 % to 95 % non condensing

Vibration

All non destructive

Safety:

 

Hi-Pot

2.3 kVrms, 60 Hz for 60 seconds

Surge

IEEE 472 and ANSI 37.90

Fused

Potential and Auxiliary Input

Warm-up:

15 seconds

 

Interface

Display:

Touch screen, color back lit LCD

Communications:

 

Serial Port

RS -232

Sensor Port

Lemo type

CT Port

3 CT Inputs (optional Clamps from Radian)

Inputs 1,2 & 3:

 

 BNC Display gate

150 Ohm pull up to 5 V, clamped at 5.7 V

 BNC Gate rate

200 nS pulse width minimum, maximum 20 Hz repetition rate.

Outputs 1, 2 & 3:
(default = 0.00001 Wh/pulse)

Programmable KH value
Open collector, clamped at 27 V
Max 2.1 MHz (200nS pulse width minimum)
Selectable Watt Hours, VAR Hours, VA Hours

Current Inputs

6 mm (<120 Amp), 8 mm (<200 Amp option)

Aux & Potential Inputs

4 mm

 

Specifications

Function

Reading

Accuracy (ppm)3
TCAL1 ± 5°C

Stability
(ppmÖ Month)

Cal Unc.
(ppm)

Temperature Coefficient6 (ppm/°C)

RD-30

RD-31

RD-33

RD-30

RD-31

RD-33

Voltage

30 V to 630 V5

200

100

50

8

4

2

30

2.5

Current

1 mA … 10 mA2

280

140

70

12

6

3

50

2.5

10 mA … 200 A

Power/Energy 3,4

1 mA … 10 mA2

400

200

100

16

8

4

80

5

10 mA … 200 A

Power Factor

> 0.5

0.04 %

0.02 %

0.01 %

 

 

 

 

 

 0.5

0.04%/2PF

0.02%/2PF

0.01%/2PF

Phase angle

0° … 360°

0.012°

0.006°

0.003°

 

 

 

 

 

 

RD-BR1 Burden & Ratio Analysis Specifications

Input Power

RD Standard connection (Allows 60-600V at Site)

Measurement Inputs

Primary CT Current:

0.1 – 3000 Amperes, 50 or 60 Hz (using probes)

Secondary CT Current:

0.01 – 20 Amperes, 50 or 60 Hz

CT Primary Probe Input Voltage:

3V RMS Max (using RR-CTA1)

Probe Scales:

10mV/A

Accuracy

Dependent on RD standard & clamp-on selected

CT Burden Testing

CT Burden Value:

0.1, 0.2, 0.5, 1.0,4.0,8.0 Ohms

Resistive Element Tolerance:

+/- 1%

Insertion Burden:

+/- 0.04 Ohms

 

Notes:
1TCAL = 23°C
2 20mA/Reading x Accuracy Specification (ppm)
3 Includes variables of Stability, Power Factor, and Traceability Uncertainty
4 (30 V … 630 V) For  1 second Test
5 Maximum 525 V at 50 Hz
6 Maximum -20 ºC … +70 ºC

Repeatability

 

 

RD-31 Menu for Measurements & Functionality

The last three digits determine the model.  The first of the last three digits determines the measurement functions. The second digit determines if the unit has a built-in computer, power analysis option and/or analog sense input. The third of the last three digits determines the current input configuration and enclosure type.

 

Specifying the first of the last three digits:  RD-31-Xxx
MODEL MEASUREMENT FUNCTIONS
RD-31-2xx Whrs, VARhrs, Volts, Amps, VAhrs, Qhrs, Watts, VARs,VA, Phase Angle, PF, Frequency
RD-31-3xx Whrs, VARhrs, VAhrs, Qhrs, Volts, Amps, Watts, VARs,VA, Vhr, Ahr, V2hr, A2hr, Phase Angle, PF, Frequency
Min & Max measurements: All indicating functions
RD-31-4xx Whrs, Volts, Amps, VARhrs, Qhrs, VAhrs, Watts, VARs,VA, Vhr, Ahr, V2hr, A2hr, Phase Angle, PF, Frequency
Min & Max: All indicating functions
AVG response: VAhrs, VA, Volts, Vhrs, Amps, Ahrs
 
Specifying the second of the last three digits:  RD-31-xXx   
-x0x No computer, No power analysis, No analog sense input
-x1x Built-in computer (with color display and WIN CE MobileSuite software)
-x2x Power analysis (Harmonics, Trending and Vector Analysis)
-x3x Built-in computer and Power analysis
-x4x Analog Sense Input (for Volts, Amps, Watts, VARs, VA)(2mA DC max)
-x5x Built-in computer and analog sense input
-x6x Power analysis and analog sense input
-x7x Built-in computer, power analysis and analog sense input
 
Specifying the third of the last three digits:  RD-31-xxX 
-xx1 120 Amp (6mm insert) current inputs, Rack Mount
-xx2 200 Amp (bolt on) current inputs, Rack Mount 
-xx3 120 Amp (6mm insert) current inputs, Portable
-xx4 200 Amp (bolt on) current inputs, Portable 

Accessories

RD-BR1

Burden & Ratio Analysis Module

RR-PCSuite

Testing and Analysis PC Software

RR-1H

Optical Pickup

RR-KYZ

Pulse Input Adapter with 4-Pin plug

RR-DS

Disk Sensor

RR-Kit

Software for Custom Application Development

Cables and Leads

 

Current Probes

 